Electrical calculations: Ohm’s law, voltage drop and cable cross-section

The basic calculations of electrical engineering at a glance: Ohm’s law with power from two known quantities, resistors in series and in parallel, voltage divider, voltage drop and minimum cross-section of a cable, plus energy and cost. Here are the formulas with examples; the calculator is in the Resinovo app, for example for electronics technicians, mechatronics technicians and industrial mechanics in training.

The formulas and a worked example

Ohm’s law and power

U = R × I · P = U × I

U voltage in V, I current in A, R resistance in Ω, P power in W. From any two known quantities (U and I, U and R, U and P, I and R, I and P, R and P) the other two follow.

Resistors in series and in parallel

R series = R1 + R2 + … · 1 / R parallel = 1 / R1 + 1 / R2 + …

Two to four resistors in Ω. In parallel the total resistance is always smaller than the smallest single resistor.

Voltage divider

U out = U in × R2 / (R1 + R2)

Unloaded. With a load resistor in parallel with R2 the output voltage drops; the app calculates both cases.

Voltage drop of a cable

ΔU = k × L × I × cos φ / (κ × A)

L single cable length in m, A cross-section in mm², κ conductivity at 20 °C (copper 56, aluminium 35 m/(Ω·mm²)), k = 2 for DC and single-phase AC (outgoing and return conductor) and √3 for three-phase. From it follows the minimum cross-section for the 3 % voltage-drop guideline, rounded up to the next standard cross-section.

Energy and cost

E = P × t · cost = E × price

P in kW, t in hours per day times days, E in kWh. The cost is only shown if a price per kWh is entered.

Worked examples

230 V / 10 A = 23 Ω · P = 2,300 W · 100 Ω + 220 Ω = 320 Ω · parallel 68.75 Ω · 24 V × 20 / (10 + 20) = 16.0 V

At 230 V a current of 10 A flows: resistance 23 Ω, power 2,300 W. Two resistors of 100 Ω and 220 Ω give 320 Ω in series and 68.75 Ω in parallel. A voltage divider of 10 kΩ and 20 kΩ on 24 V delivers 16.0 V. A copper cable of 30 m with 2.5 mm² and 16 A on 230 V AC has a voltage drop of 6.86 V (2.98 %), just below 3 %; the minimum cross-section for 3 % is 2.48 mm², which is the standard cross-section 2.5 mm². The power loss in the cable is 110 W. A device of 2.3 kW runs 8 hours on 250 days: 4,600 kWh, at €0.30 per kWh 1,380 €.

Good to know

The app deliberately does not calculate the current-carrying capacity (heating) of a cable; the relevant standards and the cable maker’s specifications apply. Conductivity, standard cross-sections and the 3 % guideline are approximations for training, not a design to VDE.

For every result the app shows the working: formula, values inserted and result, collapsible.

The calculator is part of Resinovo Basic. Before subscribing you can look at the areas of the app for five minutes free of charge, then try them free for a week.

All values are typical figures for preselection. The manufacturer’s datasheet applies to the specific grade, and sampling on the machine decides the process.

Frequently asked questions

How do I calculate the voltage drop of a cable?

With ΔU = k × L × I × cos φ / (κ × A). For AC with outgoing and return conductor k = 2, for three-phase √3. For copper κ = 56 m/(Ω·mm²) is used.

How do I choose the minimum cross-section?

The calculator rearranges the formula for A, inserts the permissible voltage drop (guideline 3 %) and rounds up to the next standard cross-section. You additionally check the heating from tables.

Why is the parallel resistance smaller than every single resistor?

Every further branch gives the current an additional path, the conductance (1/R) adds up. The total resistance therefore falls.